How to convert amps to kW (the formula)
Power is voltage times current, and a kilowatt is 1000 watts — so amps become kilowatts once you know the voltage (and, on AC, the power factor), then divide by 1000. Three cases:
| System | Formula | Example |
|---|---|---|
| DC | kW = A × V ÷ 1000 | 50 A × 240 V = 12 kW |
| AC single-phase | kW = A × V × PF ÷ 1000 | 50 A, 240 V, PF 1 = 12 kW |
| AC three-phase | kW = √3 × A × V × PF ÷ 1000 | 50 A, 480 V, PF 1 = 41.57 kW |
The √3 (about 1.732) handles three-phase, and the ÷ 1000 turns watts into kilowatts. If you want plain watts instead, skip that last step — or use the amps to watts calculator.
How many kW is X amps?
The common currents converted to kilowatts at power factor 1.0 (single-phase):
| Current | 120 V | 240 V |
|---|---|---|
| 10 A | 1.2 kW | 2.4 kW |
| 20 A | 2.4 kW | 4.8 kW |
| 30 A | 3.6 kW | 7.2 kW |
| 50 A | 6 kW | 12 kW |
| 100 A | 12 kW | 24 kW |
For three-phase, the same current gives more kilowatts because of the √3 — for example, 50 A at 480 V three-phase is about 41.57 kW, and 40 A is 33.26 kW. At the common European/industrial 415 V, 30 A three-phase is about 21.56 kW.
This is the conversion behind matching a generator (rated in kW) to a panel or breaker (rated in amps), and for sizing a service. A 200 A, 240 V service can deliver up to about 48 kW, and a 400 A service about 96 kW. Going the other way, a 20 kW generator at 240 V single-phase supplies roughly 83 A.
Power factor and three-phase
On AC, the real power in kilowatts is amps × volts × power factor ÷ 1000. Resistive loads (heaters) are power factor 1.0; motors run around 0.8, which gives fewer kilowatts for the same amps. Three-phase adds an extra √3, which is why 415 V and 480 V systems carry so much power:
20 A at 240 V:
• at PF 1.0 (resistive) → 4.8 kW
• at PF 0.8 (motor) → 3.84 kW of real power
And three-phase: 50 A at 480 V → 41.57 kW.
Amps, kW, watts, and kVA
These all connect. 1 kW = 1000 W, so for watts instead of kilowatts use amps to watts. For the reverse — a kW rating back to amps — use kW to amps. And for apparent power, remember kW = kVA × power factor; the kVA to amps page covers that side.
From amps to the circuit (size the wire and breaker)
Size the breaker and wire from the amps, not the kilowatts — and remember the NEC 125% rule for continuous loads (running three hours or more). Run the current through the Wire Size Calculator and the Breaker Size Calculator, and the AWG ampacity chart has the conductor ratings.
Frequently asked questions
ConversionsWhat is the formula to convert amps to kW?
ConversionsHow many kW is 20 amps?
ConversionsHow many kW is 50 amps?
ConversionsHow many kW is 100 amps?
ConversionsHow do I convert amps to kW for three-phase?
ConversionsDoes power factor change amps to kW?
ConversionsHow do I convert amps to kW at 240V?
ConversionsHow many kW is 30 amps?
This calculator gives estimates from the standard power formula. Real AC loads vary with power factor, and circuit sizing follows the NEC and your local authority having jurisdiction (AHJ). When in doubt, hire a licensed electrician.