For electricians & homeowners

Voltage Drop Calculator

Over a long run, voltage leaks away as heat and the far end ends up starved. This tool tells you exactly how much you lose, whether it passes the NEC 3% limit, and the wire size that fixes it.

A voltage drop calculator built for electricians — clear enough for anyone.

Voltage drop · the problem live
SOURCE ≈ 120 V RESISTANCE voltage lost as heat −8.0% AT THE HOUSE ≈ 110.4 V LIGHTS DIM 180 ft ONE-WAY FIG. 1 — VOLTAGE DROP OVER A LONG RUN DWG · VD-01 COPPER · SINGLE-PHASE · 120 V NOMINAL electricalcalcs.online

Full power leaves the source — but the long run bleeds voltage away as heat, so the house at the end is starved and the lights dim. That's the drop this tool measures.

NEC-based

Built to the current code

Transparent

Every tool shows its formula

Free & private

No signup, runs in your browser

Voltage Drop Calculator

The voltage lost over your wire run — and whether it passes the NEC 3% limit.

NEC 2026
V
A
ft

Enter one-way distance; we double it for the return automatically.

Material
Phase
Advanced — install method, continuous load, DC, power factor, temperature, parallels
°C
0.0%

Enter values to see the verdict.

Target

Max run at 3%: ft

Ampacity — can the wire carry the current?

A allowed (derated)

Step by step

How to use the voltage drop calculator

Four inputs, one clear verdict. Fill each field to match your circuit and the result updates as you type — no signup, no reset needed.

  1. 01

    Enter voltage & load

    Your system voltage (120, 240, 208…) and the current in amps. Working from watts or horsepower? Open Advanced and switch the unit — it converts for you.

  2. 02

    Set the one-way length

    Distance from source to load, one direction only — in feet. The tool doubles it for the return leg automatically, so you never count both runs yourself.

  3. 03

    Pick wire size & material

    Choose the AWG or kcmil you plan to run and whether it's copper or aluminum. Set phase to single-phase, three-phase, or DC to match the circuit.

  4. 04

    Read the verdict

    The gauge shows your percent drop with a pass, borderline, or fail call against your target, plus the voltage at the load and the farthest you can run that wire.

The concept

What is voltage drop?

Voltage drop is the loss of voltage as current travels along a conductor, caused by the wire's own resistance. It follows Ohm's law — the longer or thinner the wire, or the more current it carries, the more voltage is used up before it reaches the load.

Every conductor has resistance, so some drop is unavoidable — the goal is to keep it small. When it grows too large, the far end is starved: lights dim and flicker, motors lose torque and overheat, and electronics misbehave. Every volt lost in the wire is also energy wasted as heat, which is why long runs get a voltage-drop check, not just an ampacity check.

Voltage along the run 120V → 110.4V
V RUN → 120V supplied R 120V PANEL 110.4V LOAD

Each step is voltage handed to the wire's resistance instead of the load.

The relationship Vdrop = I × R
More current (I) or more resistance (R) — from a longer, thinner, or more heavily loaded wire — means more voltage lost before the load.

The math

Voltage drop formula.

The voltage drop formula is VD = (2 × K × I × L) ÷ CM for single-phase, where K is the conductor's resistivity (12.9 for copper, 21.2 for aluminum), I is the current in amps, L is the one-way length in feet, and CM is the wire's area in circular mils. Percent drop = (VD ÷ V) × 100.

Single-phase · K-method
VDvoltage drop
=
(
2round trip
×
Kresistivity
×
Icurrent·A
×
Llength·ft
)
÷
CMwire area
% drop = ( VD ÷ V ) × 100 K = 12.9 Cu · 21.2 Al  |  three-phase: swap 2 → 1.732
×2

Single-phase & DC

Current flows out and back, so the length that matters is twice the one-way run.

×1.732

Three-phase

That's √3. Phases share the return path, so drop is lower for the same wire.

Our calculator goes further

For AC it uses the NEC Chapter 9 impedance method — adding reactance and power factor — so it can differ by a few tenths. The example below reconciles both.

Worked example

One size up fixes it — here's the proof

Same circuit, two wires: 120 V · single-phase · 20 A · 100 ft one-way · copper. Only the conductor changes. The drop crosses back under the NEC 3% line — the exact move the calculator recommends, worked by hand and confirmed by the tool.

Where each lands on the 3% limit 0–8%
3% NEC
10 AWG 4.0% over the 3% limit Fails
8 AWG 2.6% back under the line Passes

Upsizing one size — 10 AWG to 8 AWG — moves the run left across the NEC 3% line.

10 AWGFails

10,380 circular mils

VD = (2 × 12.9 × 20 × 100) ÷ 10,380 = 4.97 V

4.97 ÷ 120 = 4.14% · tool 4.0%

8 AWGPasses

16,510 circular mils

VD = (2 × 12.9 × 20 × 100) ÷ 16,510 = 3.13 V

3.13 ÷ 120 = 2.60% · tool 2.6%

Same numerator, bigger conductor — the drop falls because the circular-mil area rose. The tool reads a hair under the textbook K-value because it uses the conductor's true AC impedance; both agree the wire goes up a size. Verify it above: enter 120 V, 20 A, 100 ft, copper.

NEC limits

What's an acceptable voltage drop?

The NEC recommends keeping voltage drop at or below 3% on a branch circuit or a feeder, and 5% for the two combined, measured to the farthest outlet. These figures are recommendations in Informational Notes — not enforceable rules — but most electricians and inspectors treat 3% as the design target.

  • Branch circuit≤ 3%
  • Feeder≤ 3%
  • Feeder + branch, combined≤ 5%

One case is mandatory

Sensitive electronic equipment under NEC 647.4(D) has an enforceable limit — 1.5% on a branch and 2.5% combined.

Voltage-drop tolerance to farthest outlet
0% 3% 5%
Ideal ≤ 3% Acceptable 3–5% Too high 5%+

Ampacity sizes a wire for heat, not distance — a long run can pass ampacity and still fail 3%. That's why voltage drop is a separate check.

What 3% equals on common systems

120 V3.60 V116.4 V at load
240 V7.20 V232.8 V at load
208 V6.24 V201.8 V at load
480 V14.40 V465.6 V at load

Factors & fixes

What affects voltage drop — and how to reduce it.

Voltage drop rises with longer runs, higher current, thinner wire, and aluminum over copper — the four levers in the formula. To cut it, the usual fix is to upsize the conductor; you can also shorten the run, raise the voltage, or split the load across circuits.

What increases it

Length

Drop rises linearly — double the run, double the drop.

more

Current

More amps through the wire, proportionally more drop.

more

Thinner wire

Smaller AWG = more resistance. Going bigger is the main lever down.

more

Aluminum

Higher resistance than copper for the same size.

more

How to reduce it

1

Upsize the conductor usual fix

More copper, less resistance, less drop — the move the calculator recommends.

2

Shorten the run

Relocate a subpanel closer to the load where the layout allows.

3

Raise the voltage

Wire a 240 V load at 240 V, not 120 V — half the current, far less drop.

4

Split or parallel

Spread the load across circuits, or run parallel conductors on large feeders.

Upsized for voltage drop? Upsize the ground too.

Per NEC 250.122(B), when you enlarge the ungrounded conductors for voltage drop, the equipment grounding conductor must grow by the same proportion. The calculator handles this automatically — the Ground wire tab flags when it's been increased.

Also matters
TemperatureHotter conductors carry slightly more resistance.
Power factorOn AC, a lower power factor raises the effective drop.
PhaseThree-phase drops ~13% less than single-phase; DC uses ×2.

Reference chart

Voltage drop chart.

Maximum one-way run for copper wire on a 120 V single-phase circuit before it exceeds the NEC 3% limit. Pick your wire size and load current for the answer. For 240 V, double the distance; for aluminum, multiply by about 0.6; for three-phase, by about 0.87.

120 V · 1∅ · Copper · 3% target
Wire size
Load current
10 AWGat20 A
75 ft
max one-way run at 3% · 120 V copper

Voltage-drop limit only. These distances assume the wire can already carry the current — they don't check ampacity. Always confirm the conductor's ampacity for your load (the calculator's Ampacity tab does this). Need a different voltage, target, or aluminum? The calculator gives an exact answer for your circuit.

Voltage drop chart — maximum one-way distance in feet to stay at or under 3% voltage drop on a 120 V single-phase copper circuit, by wire size and load current.
Wire size 15 A20 A30 A 40 A50 A60 A 100 A150 A200 A
14 AWG39 ft29 ft19 ft15 ft12 ft10 ft6 ft4 ft3 ft
12 AWG60 ft45 ft30 ft23 ft18 ft15 ft9 ft6 ft5 ft
10 AWG100 ft75 ft50 ft38 ft30 ft25 ft15 ft10 ft8 ft
8 AWG154 ft115 ft77 ft58 ft46 ft38 ft23 ft15 ft12 ft
6 AWG245 ft184 ft122 ft92 ft73 ft61 ft37 ft24 ft18 ft
4 AWG387 ft290 ft194 ft145 ft116 ft97 ft58 ft39 ft29 ft
2 AWG632 ft474 ft316 ft237 ft189 ft158 ft95 ft63 ft47 ft
1/0 AWG1,000 ft750 ft500 ft375 ft300 ft250 ft150 ft100 ft75 ft
2/0 AWG1,200 ft900 ft600 ft450 ft360 ft300 ft180 ft120 ft90 ft
4/0 AWG1,935 ft1,452 ft968 ft726 ft581 ft484 ft290 ft194 ft145 ft
250 kcmil2,308 ft1,731 ft1,154 ft865 ft692 ft577 ft346 ft231 ft173 ft
350 kcmil3,158 ft2,368 ft1,579 ft1,184 ft947 ft789 ft474 ft316 ft237 ft
500 kcmil4,444 ft3,333 ft2,222 ft1,667 ft1,333 ft1,111 ft667 ft444 ft333 ft

What is an acceptable voltage drop?

The NEC recommends 3% or less on a branch circuit or feeder, and 5% or less for the two combined, measured to the farthest outlet. Three percent is the target most electricians design to; sensitive electronic equipment under NEC 647.4(D) is held to a stricter, mandatory 1.5%.

How do you calculate voltage drop?

For single-phase, VD = (2 × K × I × L) ÷ CM — where K is 12.9 (copper) or 21.2 (aluminum), I is the current in amps, L is the one-way length in feet, and CM is the wire's circular-mil area. Divide by the source voltage for percent. The calculator above does this and refines it with AC impedance.

How can I reduce voltage drop?

Upsize the conductor (the usual fix), shorten the run, raise the system voltage (240 V instead of 120 V), or split the load across circuits. Copper also drops less than aluminum. When you upsize for voltage drop, upsize the ground wire too, per NEC 250.122(B).

Is voltage drop a code requirement?

Mostly no. The 3% and 5% figures live in NEC Informational Notes, which are recommendations, not enforceable rules. The exception is sensitive electronic equipment under 647.4(D), where the limit is mandatory. Even so, staying within 3% is standard practice and often expected by inspectors.

Do I enter one-way or round-trip length?

Enter the one-way distance — source to load, one direction. The formula's ×2 already accounts for the return leg, and this calculator doubles it automatically. Entering the round-trip length would double the drop by mistake.

Copper or aluminum — which drops more?

Aluminum drops more. For the same size and length it has higher resistance, so a copper run reaches about 1.65× as far before hitting the same limit. Aluminum is still common on larger feeders because it's lighter and cheaper — you just size up to compensate.

What's the difference for single-phase, three-phase, and DC?

The method is the same; only the multiplier changes. Single-phase and DC use ×2 for the out-and-back path; three-phase uses ×1.732 (√3). For the same wire, current, and length, a three-phase run drops roughly 13% less than single-phase.

What happens if voltage drop is too high?

The far end is starved: lights dim and flicker, heaters run cool, and motors lose torque and overheat — drawing extra current and shortening their life. Electronics can reset or misbehave, and the lost voltage is wasted as heat in the wire.

Keep going

Related electrical calculators

Voltage drop is one step in sizing a run. These follow the same job — pick the wire, protect it, and fit it in the raceway — and use the same NEC-based engine.

Browse all electrical calculators

How we keep this accurate

These calculators follow the National Electrical Code (NEC 2026): conductor properties from Chapter 9, Table 8/Table 9, and the 3% branch-circuit / 5% total voltage-drop recommendation (NEC 210.19 & 215.2 informational notes). Results are for planning and estimating. Code adoption, local amendments, temperature, and install conditions vary — always confirm against the edition your jurisdiction enforces and have work verified by a licensed electrician.

Last updated July 2026 · Verified against the National Electrical Code (NEC 2026).