For electricians & homeowners

Wire Size Calculator

Every wire is sized by two rules — it has to carry the current without overheating, and stay thick enough to hold voltage over the run. This tool takes the larger of the two and gives you the right NEC 310.16 gauge, in copper or aluminum.

A wire size calculator built for electricians — clear enough for anyone.

Wire size · the heat test live
LOAD · 40 A CARRYING 40 A THROUGH THE WALL RUNS COOL · SAFE FIG. 1 — TOO THIN OVERHEATS · SIZE UP TO RUN COOL DWG · WS-01 40 A · COPPER · 75°C electricalcalcs.online
Try it · drag the gauge at a 40 A load

Too thin for the current and a wire runs hot — the fire risk inside your wall. Size up and it runs cool. This tool finds the smallest safe gauge, and checks voltage drop on long runs.

NEC-based

Table 310.16 ampacity

Transparent

Every tool shows its formula

Free & private

No signup, runs in your browser

Wire Size Calculator

The smallest safe AWG for your load and run — sized to ampacity and voltage drop.

NEC 310.16
A
V
ft

Enter one-way distance; the round trip (×2) is applied automatically.

Material
Phase
Termination temp
%
Advanced — enter load in watts, power factor

Enter your load and run to size the wire.

Two checks — the thicker wire wins

Ampacity
Voltage drop
Drop %
at rec size
Voltage drop
volts
Required CM
circular mils
Ampacity
A allowed
Max breaker
A

How to use it

How to use the wire size calculator.

It takes four quick inputs — your load, the circuit's voltage and one-way length, and the conductor material and temperature rating. The tool then sizes the wire two ways, by ampacity and by voltage drop, and gives you the larger, safer AWG — showing exactly which one governed.

  1. 01

    Enter your load

    Type the load in amps. Not sure of the amps? Open Advanced and enter watts and volts instead — the tool converts it for you.

  2. 02

    Set voltage, phase & run

    Enter the system voltage (120, 240, 208, 480), pick 1- or 3-phase, and give the one-way length. Longer runs drive more voltage drop.

  3. 03

    Pick material & temperature

    Choose copper or aluminum and the termination column (60, 75, or 90 °C) — usually 75 °C. Flag continuous loads to size at 125%.

  4. 04

    Read your size — and why

    Get the recommended AWG instantly, plus whether ampacity or voltage drop governed — so you know what's driving the size, not just the number.

The core idea

What determines your wire size

Enter your circuit once — the calculator runs both checks and hands you the thicker, safer gauge.

Wire size is set by the larger of two requirements. Ampacity means the conductor must carry the current without overheating; voltage drop means it must stay thick enough to hold voltage over the run. On short runs ampacity usually governs — on long runs, voltage drop does.

Two rules size every wire — the thicker one wins

Ampacity

The conductor must carry the load without overheating.

↑ higher current

Voltage drop

The conductor must stay thick enough over the distance.

↑ longer runs
SHORT RUNcrossoverLONG RUN
Ampacity usually governsVoltage drop usually governs
The rule

Wire size = the larger of  ampacity size  and  voltage-drop size

The method

How wire size is calculated

There's no single wire size formula — the calculator runs two checks and keeps the larger result. Ampacity is a table lookup; voltage drop is a real equation. Whichever demands the thicker conductor is your answer.

Example circuit120 V · 30 A · 120 ft · copper · 3%

Check 1 · Ampacity

Smallest AWG whose NEC 310.16 rating is ≥ your load at the terminal temperature — then capped by 240.4(D).

30 A → 10 AWG@ 75 °C

A table lookup — not a formula.

Check 2 · Voltage drop

CM= 2 × K × I × L V × %
2 round trip (1.732 for 3∅) K 12.9 Cu · 21.2 Al I amps · L one-way ft
≥ 25,800 CM → 6 AWG
take the larger 10 AWG vs 6 AWG 6 AWG voltage-drop-limited

Worked example

On a long run, voltage drop wins

Same circuit, worked end to end: 30 A over a 120 ft copper run at 120 V. Ampacity alone allows 10 AWG — but at that length its voltage drop hits 7.5%, past the 3% target. Sizing for voltage drop forces 6 AWG.

The circuit 120 V1∅30 A120 ft one-waycopper75 °C≤ 3% drop
upsize for voltage drop NEC 3% 6 AWG · 2.95% 10 AWG · 7.46% 0% 8%+
10 AWG ampacity's pick — sized for current only 7.46% Fails 3%
6 AWG upsized so the run holds voltage 2.95% Passes

Check 1 · Ampacity

Load 30 A → need a conductor rated ≥ 30 A.

At 75 °C that's 10 AWG (30 A, per 240.4(D)).

Ampacity wants 10 AWG

Check 2 · Voltage drop

Allowed drop = 3% × 120 V = 3.6 V.

CM = 2 × 12.9 × 30 × 120 ÷ 3.6 = 25,800.

Smallest AWG ≥ 25,800 CM = 6 AWG (26,240).

Voltage drop wants 6 AWG

take the larger

6 AWG — voltage-drop-limited. Both checks pass at 6 AWG; ampacity's 10 AWG would drop 7.5% over 120 ft, so the longer run is what drives the size up.

The code behind it

Ampacity & the NEC rules that size wire

Ampacity is the current a conductor carries continuously without overheating, from NEC Table 310.16. It's listed in three temperature columns — 60, 75, and 90 °C — but you rarely use the 90 °C number: your terminations set the column, and it's usually 75 °C.

★ Usually use the 75 °C column
NEC Table 310.16 copper ampacity by termination temperature column
Copper 60 °C 75 °C 90 °C
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
2 AWG95115130

Amps at each column, copper. Aluminum runs lower — about two sizes larger for the same load.

240.4(D)

Small-conductor cap

Max breaker is 15 A on 14 AWG, 20 A on 12, 30 A on 10 — regardless of higher ampacity. Why branch circuits are 14/15, 12/20, 10/30.

334.80

NM-B / Romex

Sized from the 60 °C column even though the wire is 90 °C-rated — so 12 AWG NM-B is 20 A, not 25 A.

310.15(C)

Derating

More than 3 current-carrying conductors bundled, or high ambient heat, lowers ampacity — upsize to compensate.

210.19(A)

Continuous loads

Size the conductor and breaker for 125% of any load running 3+ hours continuously.

250.122

Ground wire

Upsize the equipment grounding conductor proportionally when you upsize conductors for voltage drop.

Levers

What pushes wire size up — and how to bring it down

Four things drive wire size up: more current, longer runs, aluminum instead of copper, and lower voltage. The biggest lever to bring it back down is voltage — running 240 V instead of 120 halves the current and cuts voltage drop to a quarter.

What pushes it up

  • More currentHigher load needs more ampacity.
  • Longer runVoltage drop grows with every foot.
  • AluminumAbout two sizes larger than copper.
  • Lower voltageSame watts pulls more amps.

How to bring it down

  1. 1Raise the voltage240 V halves the current, quarters the drop.
  2. 2Shorten the runRelocate the panel or a subpanel closer.
  3. 3Use copperAbout two sizes smaller than aluminum.
  4. 4Split the loadSeparate circuits each carry less.

The biggest lever · voltage

Double the voltage, quarter the drop

Voltage drop falls with the square of the voltage — so the same load on 240 V often drops the wire two full sizes versus 120 V.

120 V30 A
240 V15 A

Same 3,600 W load · relative voltage drop

Also in play

310.15(C)

High ambient heat or more than 3 bundled conductors derate ampacity — upsize.

210.19(A)

Loads running 3+ hours are continuous — size at 125%.

Drop target

3% is the usual aim; 5% total is the NEC ceiling.

Phase

3-phase drops less — the multiplier is ×1.732, not ×2.

Reference

Wire size chart — what size wire for the amps

Pick a load current, material and temperature column to get the wire size by ampacity (NEC 310.16, with the 240.4(D) cap applied). On long runs, check the calculator above — voltage drop can push the size larger.

Load current
Material
Termination temp

Minimum wire size

30 A · copper

10 AWG

75 °C column · 240.4(D) applied · by ampacity

Ampacity only. A longer run may need a larger conductor for voltage drop — size the full circuit in the calculator above.

Wire size by amperage (NEC 310.16, 75 °C column, 240.4(D) applied)
Load (amps)Copper wire sizeAluminum wire size
15 A14 AWG12 AWG
20 A12 AWG10 AWG
30 A10 AWG8 AWG
40 A8 AWG8 AWG
50 A8 AWG6 AWG
60 A6 AWG4 AWG
70 A4 AWG3 AWG
80 A4 AWG2 AWG
90 A3 AWG2 AWG
100 A3 AWG1 AWG
110 A2 AWG1/0 AWG
125 A1 AWG2/0 AWG
150 A1/0 AWG3/0 AWG
175 A2/0 AWG4/0 AWG
200 A3/0 AWG250 kcmil
What size wire do I need for a 50 amp circuit?

For a 50 A circuit the common choice is 6 AWG copper or 4 AWG aluminum. (8 AWG copper is rated 50 A at 75 °C, but continuous loads like EV chargers, and runs over about 100 ft, push most 50 A circuits up to 6 AWG.)

What about 30, 100, or 200 amps?

At the 75 °C copper column: 30 A → 10 AWG, 60 A → 6 AWG, 100 A → 3 AWG. A 200 A dwelling service is commonly 2/0 copper or 4/0 aluminum under the NEC 83% rule. Aluminum runs about two sizes larger throughout.

How much bigger does aluminum need to be?

About two AWG sizes larger than copper for the same load — aluminum carries roughly 61% of copper's current. So where copper needs 6 AWG, aluminum needs 4 AWG.

What is ampacity?

Ampacity is the current a conductor can carry continuously without passing its temperature rating (NEC Table 310.16). It's one of the two things that set wire size — the other is voltage drop.

Do I use the 60, 75, or 90 °C column?

Almost always the 75 °C column — your terminations set it (110.14(C)). The 90 °C column is only a starting point for derating, and NM-B/Romex is sized from the 60 °C column.

When does voltage drop change the wire size?

On long runs. A rough trigger: when the one-way length in feet exceeds the system-voltage number, voltage drop often forces a larger wire than ampacity alone — the calculator checks both and keeps the larger.

Do I upsize for a continuous load?

Yes. For loads running 3+ hours (EV chargers, heaters), size the conductor and breaker for 125% of the load (NEC 210.19(A)). A 40 A continuous load needs a 50 A circuit.

Is it OK to use a bigger wire than required?

Yes — you can always go larger, never smaller. Oversizing costs more and can crowd terminals, but it's safe and lowers voltage drop. Undersizing is a fire risk.

Keep going

Related electrical calculators

Sizing the conductor is one step in the circuit. These pick up where it leaves off — check the run, protect it, and fit it in the raceway — and run on the same NEC-based engine.

Browse all electrical calculators

How we keep this accurate

These calculators follow the National Electrical Code (NEC 2023): ampacity from Table 310.16, the 240.4(D) small-conductor rule, 110.14(C) terminations, and the 3% branch / 5% total voltage-drop guidance (210.19 & 215.2 informational notes). Results are for planning and estimating. Code adoption, local amendments, and field conditions vary — verify with your AHJ and a licensed electrician before installation.