Power · correction

Power Factor
Calculator

Find your power factor and the full power triangle — then size the capacitor to correct it. Raising power factor shrinks the apparent power (kVA) and current you're billed for, without changing the real work (kW). PF = kW ÷ kVA

Built for plant and panel work — clear enough for anyone.

The power triangle, corrected live
FIG. 1 — POWER FACTOR CORRECTION θ PF 0.75 REAL · 100 kW 133.3 kVA 88.2 kVAR real power fixed · reactive & apparent shrink as PF improves
Raise the power factor →

Same 100 kW of real work at three power factors. As PF climbs toward 1.0, the reactive power (kVAR) and apparent power (kVA) collapse toward the real power — that's what correcting the power factor does.

PF · kVA · kVAR

the full power triangle

Correction capacitor kVAR

the exact size to add

Free & private

no signup, runs in your browser

Dr. Artie Vance

Written & reviewed by Dr. Artie Vance — Ph.D. in Physics, MIT · 14 years' experience

View articles

Artie has taught physics and electrical theory for over a decade and consulted on real-world electrical design — so every tool here is grounded in both the theory and the field.

Every calculator on this site is checked against the 2023 NEC before it ships — if the math doesn't match the code, it doesn't go live.

University physics lecturer·Consulted on commercial electrical systems·Last reviewed Jul 2026

Power Factor Calculator

Find power factor — and size the capacitors to correct it.

cos φ
kW
kVA
00.850.951.0

Enter values to find the power factor.

The power triangle

Power factor
real ÷ apparent
Reactive power
the part to cancel

How to use it

How to use the power factor calculator

Pick a mode: find your power factor from real and apparent power, or correct it to a target. Enter what you know, set the voltage and phase, and read the full power triangle — or the exact capacitor kVAR you need to add.

  1. 01

    Choose a mode

    Find power factor from your numbers, or correct it — size the capacitor to hit a target PF.

  2. 02

    Enter what you know

    To find: kW plus apparent power (kVA, or V & I). To correct: your load, current PF, and target PF.

  3. 03

    Set voltage, phase & frequency

    So it can size the capacitor — the required kVAR, the microfarads, and the before/after current.

  4. 04

    Read the result & size it

    Get the full power triangle and PF — or the exact capacitor kVAR to add — then size the wire or breaker.

The core idea

Power factor, and the power triangle

How much of the supplied power actually does work.

Power factor is the ratio of real power (kW) to apparent power (kVA) — how much of what your supply delivers actually does work. PF = cos θ, the angle of the power triangle. At PF 0.8, only 80% of the supplied power is useful.

The power triangle — power factor is the angle

θ REAL 100 kW REACTIVE 88.2 kVAR APPARENT 133.3 kVA PF = cos 41.4° = 0.75
Power factorPF = cos θ = kW ÷ kVA
Real powerkW = kVA × PF
ReactivekVAR = kW × tan θ
The ratio0.75 → 75% useful

PF runs from 0 to 1 (or 0–100%). At 1.0 all the supplied power does work; below ~0.9 the supply carries extra reactive current for no useful output.

Lagging · inductive

Motors, transformers, welders, coils. Current lags the voltage — the usual cause of a poor power factor, and what you correct by adding capacitors.

Leading · capacitive

Over-correction, or long lightly-loaded cables. Current leads the voltage — utilities penalise this too, and it can push voltage too high.

The rule

PF = cos θ = kW ÷ kVA lagging (inductive) is the common case; correct it with capacitors

The method

The power factor formulas

Two jobs, two families of formula. Find splits real and apparent power into the triangle — power factor is their ratio. Correct sizes the capacitor: the reactive power (kVAR) it must supply to raise the power factor to your target.

Find · the trianglethe ratio
power factor

PF = kW ÷ kVA = cos θ

reactive

kVAR = √(kVA² − kW²)

apparent

kVA = kW ÷ PF

Correct · the capacitorcapacitor kVAR
capacitor kVAR

Qc = kW × (tan φ₁ − tan φ₂)

capacitance

C = Qc × 10⁹ ÷ (2π f V²)

the bridge Qc = kVAR₁ − kVAR₂ the capacitor cancels the reactive power
φ · √3

Angle & phase — φ = arccos(PF). For three-phase, kVA = √3 × V × I ÷ 1000 (line-to-line).

µF

Capacitance — 1-phase formula shown; three-phase delta = (Qc/3) × 10⁹ ÷ (2π f VLL²) per phase.

Worked 100 kW · PF 0.75 → 0.95 = 55.3 kVAR of capacitors
Remember

PF = kW ÷ kVA · correction removes reactive power, not real power · target 0.95 to clear penalties

Worked example

Correct 100 kW from 0.75 to 0.95

A 100 kW load at 0.75 power factor pulls 133 kVA and 160 amps. Add a 55 kVAR capacitor bank and the power factor climbs to 0.95 — the apparent demand and line current both drop about 21%, with no change to the real work.

Correct 100 kWPF 0.75 → 0.95480 V3-phase
Before · PF 0.75
133.3 kVA 88.2 kVAR 160.4 A
After · PF 0.95
105.3 kVA 32.9 kVAR 126.6 A
Apparent demand
133.3 → 105.3 kVA −21%
Line current
160.4 → 126.6 A −34 A

angle 1 φ₁ = arccos 0.75 = 41.4° · tan = 0.882

angle 2 φ₂ = arccos 0.95 = 18.2° · tan = 0.329

capacitor Qc = 100 × (0.882 − 0.329) = 55.3 kVAR

the answer

One 55 kVAR capacitor bank raises the power factor from 0.75 to 0.95 — dropping apparent demand from 133 to 105 kVA and line current 34 A, with the real work unchanged at 100 kW. Less strain on transformers and cables, and it clears the utility's penalty threshold.

The reference

Power factor by load & why it matters

Most loads sit below 1.0 — motors and welders drag it down, while resistive loads sit at unity. Below about 0.90, utilities often penalise or bill on kVA demand, so 0.95 is the usual correction target.

★ induction motors — the usual culprit
Typical power factor by load type
Load typeTypical PF
Resistive heater · incandescent1.0
Induction motor — full load0.85
Induction motor — half load0.70
Welder · arc furnace0.5–0.7
Fluorescent · LED lighting~0.9
Fully-loaded transformer0.98

Typical values — nameplate or measured PF is always better. A motor at part load is the biggest drag.

TARGET

Aim for 0.95

Clears most penalty thresholds with margin. Chasing a full 1.0 risks over-correction into a leading PF.

DIRECTION

Lagging vs leading

Motors and coils lag (the common case); too many capacitors lead. Both are penalised — don't overshoot.

PENALTY

Utility charges

Many utilities bill on kVA demand or add a surcharge below 0.90–0.95. Correction avoids both.

HARMONICS

VFDs & non-linear loads

This is displacement PF. Heavy harmonics distort true PF — do a power-quality study before adding capacitors.

CONVERT

Amps, kW, kVA?

For amps ↔ kVA ↔ kW use the Ampere calculator; for watts → amps, Watt-to-Amp →

What affects it

What drags it down — and how you fix it

Power factor drops when reactive loads dominate — lightly-loaded motors, transformers, welders, and VFDs. The fix is capacitors that supply that reactive power locally, sized to a sensible target so you don't over-correct.

What drags it down

the reactive loads

  • Lightly-loaded motorsInduction motors at part load are the #1 cause — they draw magnetising current whether or not they're doing work.
  • Transformers at light loadA transformer's magnetising current dominates when it's lightly loaded, pulling the power factor down.
  • Welders & furnacesWelders, arc furnaces, and induction heating are inherently low-power-factor reactive loads.
  • VFDs & non-linear loadsDrives and electronics draw distorted current — a low power factor plus harmonics.

How you fix it

supply the reactive power

  1. 01
    Capacitor banksAdd capacitors that supply the reactive power locally, so the supply doesn't have to.
  2. 02
    Individual vs centralAt the motor switches with the load; at the switchgear (central) is cheaper to install.
  3. 03
    APFC panelsAutomatic PF correction switches capacitor steps in and out as the load varies.
  4. 04
    Size to a targetCorrect to about 0.95 — enough to clear penalties without over-correcting.

The point

Correction cuts the kVA and current — not the kW

Capacitors supply the reactive power locally, so the supply carries less. The apparent power (kVA) and line current fall; the real work (kW) — and your kWh — stay exactly the same.

Don't over-correct. Too many capacitors swing you to a leading power factor — also penalised, and it can push voltage too high. With VFDs and non-linear loads, plain capacitors can resonate with harmonics — do a power-quality study before sizing a bank.

Quick chart

The correction-factor table

The industry shortcut: find your current power factor and your target, read the multiplier, and multiply by your load in kW to get the capacitor kVAR. From 0.75 to 0.95 the multiplier is 0.553 — so 100 kW needs 55.3 kVAR.

kW

Multiplier k = tan(arccos PF₁) − tan(arccos PF₂). Capacitor kVAR = k × kW.

Capacitor needed

55.3 kVAR

0.553 × 100 kW

Multiplier k — current PF → target PF

Power factor correction multiplier by current power factor and target power factor
Current PF→ 0.90→ 0.95→ 1.00
0.700.5360.6921.020
0.720.4800.6350.964
0.750.3980.5530.882
0.780.3180.4740.802
0.800.2660.4210.750
0.820.2140.3690.698
0.850.1350.2910.620
0.880.0550.2110.540
0.900.0000.1560.484

Read your current PF row, your target column, then multiply by your kW load. Capacitor kVAR = k × kW.

Power factor correction factor table: multiplier to raise power factor to 0.85, 0.90, 0.92, 0.95, 0.98, or 1.00
Current PF→0.85→0.90→0.92→0.95→0.98→1.00
0.600.7140.8490.9071.0051.1301.333
0.650.5490.6850.7430.8400.9661.169
0.700.4000.5360.5940.6920.8171.020
0.750.2620.3980.4560.5530.6790.882
0.800.1300.2660.3240.4210.5470.750
0.850.0000.1350.1940.2910.4170.620
0.900.0000.0000.0580.1560.2810.484
What is power factor?

Power factor is the ratio of real power (kW) to apparent power (kVA) — how much of the power your supply delivers actually does useful work. It runs from 0 to 1; at 0.8, only 80% of the supplied power is doing work.

How do I calculate power factor?

Divide real power by apparent power: PF = kW ÷ kVA. It's also the cosine of the phase angle. From measurements, find kVA first (kVA = V × I ÷ 1000, × √3 for three-phase), then divide the kW into it.

What is a good power factor?

Above 0.95 is excellent, and most utilities want at least 0.90 to 0.95. Below about 0.85 is poor — you're drawing extra reactive current for no useful output, and you may face penalties.

How do I improve power factor?

Add capacitors that supply the reactive power right at the load, so the supply carries only the real kW. For a whole plant, an automatic capacitor bank (APFC) steps in and out as the load varies.

What size capacitor do I need?

The required capacitor kVAR = kW × (tan φ₁ − tan φ₂), where φ is arccos of each power factor. Or read the correction-factor table: multiply your kW by the factor for your current and target PF.

What's the difference between leading and lagging power factor?

Lagging means the current lags the voltage — the usual case with inductive loads like motors. Leading means it leads, from capacitive loads or over-correction. Utilities penalise both.

Does correcting power factor save money?

It lowers your apparent (kVA) demand and line current, and clears utility power-factor penalties — but it doesn't reduce the real energy (kWh) you use. Whether it pays back depends on your tariff.

Why do utilities penalise low power factor?

A low power factor means the grid must carry extra current for the same real work — sizing transformers and cables for capacity that does nothing useful. Many utilities bill on kVA demand or add a surcharge to recover that cost.

Keep going

Related electrical calculators

Power factor sits between the current and the power. These pick up on either side: convert amps to kVA and kW, turn watts into amps, and size the conductor.

Browse all electrical calculators

How we keep this accurate

Calculations use the standard relationships — PF = kW ÷ kVA, Qc = kW × (tan φ₁ − tan φ₂), × √3 for three-phase — and give displacement power factor. Results are for planning and screening. Capacitor ratings, harmonics, switching, and utility tariffs vary — confirm with equipment data and a licensed engineer before installing correction.