Amps · power · current
Ampere
Calculator
Convert between amps, kilowatts, and kilovolt-amps for any circuit. The key: kVA is the total power your supply carries; kW is the useful part — and kW = kVA × PF. Works for DC, single- and three-phase, plus horsepower.
An ampere calculator built for pros — clear enough for anyone.
Same amps and volts means the same 24 kVA — but a lower power factor means less of it is real, useful kW. The gap is reactive power the supply still has to carry.
Amps ↔ kW ↔ kVA
convert in any direction
DC · 1φ · 3φ · HP
every system & motor
Free & private
no signup, runs in your browser
Ampere Calculator
Convert between amps, kW, kVA and HP for DC and AC single- or three-phase.
A starting point — final size depends on continuous load, derating & terminal ratings.
Enter values to convert.
The power triangle
Next: size the circuit
A starting point — the final size still depends on continuous-load 125%, conductor derating and terminal ratings.
Same apparent power (kVA), different voltage — tap to use
Method — the formula for this case
kVA is apparent power and never uses power factor. kW is real power = kVA × PF. Reactive kVAR = √(kVA² − kW²). Three-phase L-L uses √3 (1.732); L-N uses 3. DC has no reactive power (kVA = kW). HP uses 746 W/HP and efficiency η.
For planning and conversion. For breaker and conductor sizing apply the relevant code rules (continuous-load 125%, derating, terminal ratings; motors per Art. 430). Three-phase assumes a balanced system. Verify against the adopted code and consult a licensed electrician.
How to use it
How to use the ampere calculator
Tell it what you know — amps, kilowatts, kilovolt-amps, or horsepower — then add the voltage and phase. It converts between all of them instantly, keeping apparent (kVA) and real (kW) power straight, and points you to sizing the wire and breaker.
-
01
Pick what you know
Choose your starting point — amps, kW, kVA, or horsepower. The tool converts to the rest.
-
02
Enter it & the voltage
Type the value and the circuit voltage. You always need the voltage to move between current and power.
-
03
Set the phase & power factor
Pick DC, single-, or three-phase. For kW and motors, add the power factor — kVA doesn't need it.
-
04
Read the conversions & size it
Get amps, kW, and kVA at once — then size the wire, breaker, or convert watts in a tap.
The core idea
kVA, kW, and the power factor
One current, three ways to measure the power.
Amps and volts set the apparent power (kVA) — the total your supply must carry. The power factor then splits it: the real power (kW) that does work, and the reactive power (kVAR) that doesn't. kW = kVA × PF.
The power triangle — power factor is the angle
Amps set the apparent power — kVA = V × I ÷ 1000. The power factor then decides how much of it is real, working kW.
For three-phase, multiply by √3. Use the line-to-line voltage: kVA = √3 × V × I ÷ 1000 (√3 ≈ 1.732). The same power spread across three conductors draws less current per phase than single-phase.
kW = kVA × PF — kVA = (√3 × V × I) ÷ 1000 for three-phase
The method
The ampere formulas
Two families of formula, split by power factor. Apparent power (kVA) comes straight from amps and volts — no power factor. Real power (kW) is the apparent power times the power factor. For three-phase, multiply by √3.
kVA = (A × V) ÷ 1000
A = (kVA × 1000) ÷ V
kW = (PF × A × V) ÷ 1000
A = (kW × 1000) ÷ (V × PF)
Three-phase — multiply by √3 (1.732) using the line-to-line voltage; use 3 instead of √3 for line-to-neutral.
Motors — A = (HP × 746) ÷ (V × η × PF), where η is efficiency; ×√3 for three-phase.
kVA never uses power factor · kW = kVA × PF · apparent is what the supply carries, real is what does work
Worked example
Convert 100 amps to kVA and kW
At 240 V single-phase, 100 amps is 24 kVA of apparent power — the total the supply carries. At a power factor of 0.8, 19.2 kW of that is real, working power. The rest is reactive.
1φ kVA 100 × 240 ÷ 1000 = 24 kVA
1φ kW 24 × 0.8 = 19.2 kW
3φ kVA √3 × 150 × 440 ÷ 1000 = 114.3 kVA
100 A at 240 V is 24 kVA apparent — the total the supply must carry — of which 19.2 kW is real, working power at PF 0.8. Size generators and transformers by the kVA; the kW is what does the work and shows on the bill.
The reference
kVA vs kW & the fine print
The one distinction that matters: apparent power (kVA) is the total your supply must carry — it sizes generators, transformers, and UPS units. Real power (kW) is the useful part that does work and shows on the bill. Power factor connects them.
| Voltage | Type | Typical use |
|---|---|---|
| 120 V | AC · 1-phase | Home outlets, lighting |
| 208 V | AC · 3-phase | Commercial (line-to-line) |
| 240 V | AC · 1-phase | Dryers, ranges, EV |
| 400 V | AC · 3-phase | Industrial IEC (L-L) |
| 415 V | AC · 3-phase | Industrial (line-to-line) |
| 440 V | AC · 3-phase | Motors, industrial |
| 480 V | AC · 3-phase | Industrial US (line-to-line) |
| 12–48 V | DC | Battery, solar, telecom |
For three-phase, use the line-to-line voltage with √3; for line-to-neutral, use ×3.
Typical values
Resistive (heaters) 1.0 · induction motors 0.8–0.85 · LED & electronics ~0.9. kVA ignores it; kW depends on it.
Motor sizing
Computed motor amps are an estimate. NEC uses table full-load values (430.248 / 430.250) for wire & breaker, at 125%. Size the breaker →
√3 or 3
Line-to-line uses √3 (≈1.732); line-to-neutral uses 3. The same power draws less current per conductor.
Correction
A low power factor draws more amps for the same kW — and can mean utility penalties. Check power factor →
Have watts?
Converting plain watts (W) or kW straight to amps? Use the Watt-to-Amp calculator →
What affects it
What moves the numbers — and the common mistakes
The conversion shifts with three things — the voltage, the power factor (which changes kW but never kVA), and the phase. The mistakes cluster there too: applying power factor to kVA, or mixing up apparent and real power.
What moves the numbers
the levers
- VoltageInverse with current — the same power draws fewer amps at higher voltage. It scales the kVA directly.
- Power factorChanges the real kW only — kVA is fixed by amps and volts. A lower PF means less useful kW.
- PhaseThree-phase divides by √3, so the same power draws less current per conductor than single-phase.
- Efficiency (motors)HP is output — input amps use efficiency and PF. A less efficient motor draws more current.
Common conversion mistakes
what trips people up
- 01Don't apply PF to kVAkVA is apparent power — amps × volts, full stop. Power factor only affects kW.
- 02Don't size by the wrong powerRate generators, transformers, and UPS by kVA, not kW — kW undersizes them.
- 03Don't use the wrong phaseSingle vs three-phase, and L-L vs L-N, change the √3 factor and your amps.
- 04Don't forget motor efficiencyHP is output; input amps use efficiency and PF, or they come out too low.
The rule
kVA is fixed — power factor only moves the kW
Amps × volts (× √3 for three-phase) sets the apparent power, full stop. The power factor then decides how much of it is real, working kW — it never touches the kVA.
Size a generator by the wrong number and you'll undersize it. A 100 kVA load at PF 0.8 is only 80 kW of real power — but the generator still has to be rated for the full 100 kVA, reactive part included.
Quick chart
Amps to kVA, at a glance
Pick amps, voltage, and phase to get the apparent power (kVA) — or switch to real power (kW) or reverse it. For the common one — 100 amps at 240 V single-phase — that's 24 kVA.
kVA is apparent power — it doesn't use power factor. Switch to kW to apply it.
Apparent power
24.0 kVA
100 A × 240 V ÷ 1000
Amps → kVA at 240 V
| Amps | 1-phase (kVA) | 3-phase (kVA) |
|---|---|---|
| 10 A | 2.4 | 4.2 |
| 20 A | 4.8 | 8.3 |
| 30 A | 7.2 | 12.5 |
| 50 A | 12.0 | 20.8 |
| 100 A | 24.0 | 41.6 |
| 150 A | 36.0 | 62.4 |
| 200 A | 48.0 | 83.1 |
| 400 A | 96.0 | 166.3 |
kVA = amps × volts ÷ 1000 (× √3 for three-phase). For real power in kW, multiply by the power factor.
| Amps | 208 V | 240 V | 400 V | 480 V |
|---|---|---|---|---|
| 50 A | 18.0 kVA | 20.8 kVA | 34.6 kVA | 41.6 kVA |
| 100 A | 36.0 kVA | 41.6 kVA | 69.3 kVA | 83.1 kVA |
| 200 A | 72.1 kVA | 83.1 kVA | 138.6 kVA | 166.3 kVA |
| 400 A | 144.1 kVA | 166.3 kVA | 277.1 kVA | 332.6 kVA |
How do I convert amps to kVA?
Multiply amps by volts and divide by 1,000: kVA = (A × V) ÷ 1,000. For three-phase, multiply by √3 (1.732). Apparent power (kVA) doesn't use power factor — that's only for kW.
What's the difference between kVA and kW?
kVA is apparent power — the total your supply must carry. kW is real power — the useful part that does work and shows on the bill. They're equal only at power factor 1.0; otherwise kW = kVA × PF.
How do I convert amps to kW?
kW = (PF × A × V) ÷ 1,000 for single-phase, or × √3 for three-phase. Unlike kVA, kW needs the power factor — 1.0 for resistive loads, about 0.8 for motors.
How do I convert kVA to amps?
Reverse the formula: A = (kVA × 1,000) ÷ V for single-phase, or ÷ (√3 × V) for three-phase. A 100 kVA three-phase load at 400 V draws about 144 A.
Do I need power factor to find kVA?
No. kVA is apparent power — just amps × volts (× √3 for three-phase). Power factor only comes in when you convert to real power (kW). Applying it to kVA is the most common mistake.
How do I convert horsepower to amps?
A = (HP × 746) ÷ (V × efficiency × PF), and × √3 for three-phase. HP is the motor's output, so efficiency and power factor account for the extra current the motor actually draws.
What's the three-phase formula?
For three-phase line-to-line: kVA = (√3 × V × I) ÷ 1,000, where √3 ≈ 1.732. If your voltage is measured line-to-neutral, use 3 instead of √3.
Why does three-phase use √3?
Three-phase power is delivered across three conductors offset by 120°. The √3 (≈1.732) factor accounts for how those phases combine, so the same power draws less current per conductor than single-phase.
Keep going
Related electrical calculators
You've got the amps — now put them to work. These pick up from there: convert watts, size the wire, and protect the circuit, all on the same NEC-based engine.
How we keep this accurate
Conversions use the standard relationships — kVA = V × I ÷ 1000, kW = kVA × PF, × √3 for three-phase. Sizing tools follow the National Electrical Code (NEC 2026). Results are for planning and estimating. Code adoption, local amendments, and field conditions vary — verify with your AHJ and a licensed electrician before installation.
Last updated September 2026 · Verified against the National Electrical Code (NEC 2026).