Size the feeder
Conversions · Apparent power

kVA to Amps Calculator — Single-Phase, Three-Phase & Transformers

To convert kVA to amps, divide by the voltage — and by √3 for three-phase. No power factor needed, because kVA is apparent power. Single-phase: amps = kVA × 1000 ÷ V. Three-phase: ÷ (√3 × V). Enter your numbers below.

Dr. Artie Vance Written and reviewed by Dr. Artie Vance, Ph.D. Physics, MIT · 14 years' experience · Updated August 26, 2026
kVA → Amps Calculator Live
Convert kVA to amps
Pick the system, then enter the kVA and voltage. No power factor — kVA already includes it.
Full-load current 90.21A
Three-phase: 75 × 1000 ÷ (1.732 × 480) = 90.21 A
Sizing a transformer feeder? Size the wire & breaker →
Three-phase uses line-to-line voltage. Have a kW rating instead? Use the kW to amps calculator — that one needs power factor.

How to convert kVA to amps

kVA is apparent power — volts times amps directly — so the current comes straight from the voltage, with no power factor in the way. Multiply kVA back to VA (× 1000), then divide by the voltage:

SystemFormulaExample
AC single-phaseI = kVA × 1000 ÷ V10 kVA, 240 V = 41.67 A
AC three-phaseI = kVA × 1000 ÷ (√3 × V)75 kVA, 480 V = 90.21 A

The × 1000 turns kilovolt-amps into volt-amps. The √3 (about 1.732) in the three-phase formula comes from three-phase geometry — the same kVA draws fewer amps per line on a three-phase system.

kVA vs kW: why there's no power factor here

This is the mix-up worth clearing up. kVA is apparent power — the total the conductors actually carry. kW is real power — the useful work — and the two are linked by power factor: kW = kVA × PF. Because kVA already reflects the full current, you don't apply power factor when converting kVA to amps. Power factor only enters when you start from kW.

The 100 kVA example

A 100 kVA load at a 0.8 power factor is 80 kW of real power — but it still draws the amps of the full 100 kVA. Size conductors and breakers from the kVA (the current), not the kW. If your number is in kW, run it through the kW to amps calculator instead.

Single-phase vs three-phase

Single-phase (120/240 V) divides by the voltage; three-phase (208/480 V) divides by an extra √3, so the same kVA pulls fewer amps per conductor. Here's 10 kVA across common systems:

10 kVAVoltageAmps
Single-phase120 V83.33 A
Single-phase240 V41.67 A
Three-phase208 V27.76 A
Three-phase480 V12.03 A

Transformer full-load amps chart (kVA to amps)

This kVA to amps chart gives the three-phase full-load current for standard transformer sizes at 208 V and 480 V — the numbers behind "75 kVA to amps" and the like:

Transformer208 V (3φ)480 V (3φ)
15 kVA41.64 A18.04 A
30 kVA83.27 A36.08 A
45 kVA124.91 A54.13 A
75 kVA208.18 A90.21 A
112.5 kVA312.27 A135.32 A
150 kVA416.36 A180.42 A
225 kVA624.54 A270.63 A
300 kVA832.72 A360.84 A

For single-phase transformers, the same formula applies without √3 — a 25 kVA single-phase transformer at 240 V is 104.17 A, and a 50 kVA is 208.33 A.

Generators & UPS units

Generators and UPS systems are usually rated in kVA, not kW — so this same calculator turns a genset or UPS rating straight into the output amps you can pull, which is what you match to a transfer switch, feeder, or panel. A 30 kVA standby generator at 208 V three-phase, for example, delivers about 83.27 A per line.

From kVA to the feeder (size the wire and breaker)

A transformer's secondary full-load amps — the number this calculator gives — is what sizes the secondary feeder and its protection. Continuous loads still follow the NEC 125% rule, and transformer overcurrent protection has its own rules in NEC 450.3, so a big install is worth an electrician's eye. Run the full-load amps through the Wire Size Calculator and the Breaker Size Calculator, and the AWG ampacity chart has the conductor ratings.

Frequently asked questions

ConversionsWhat is the formula to convert kVA to amps?
Amps = kVA × 1000 ÷ volts for single-phase, or ÷ (√3 × volts) for three-phase. There is no power factor, because kVA is apparent power.
⚡ Size the feeder →
ConversionsHow many amps is 1 kVA?
About 4.17 amps on a single-phase 240-volt system (1000 ÷ 240). At 120 volts it is 8.33 amps.
ConversionsDoes kVA to amps use power factor?
No. kVA is apparent power and already reflects the full current, so no power factor is applied. Power factor only matters when you convert from kW, which is real power.
ConversionsHow many amps is a 75 kVA transformer?
A 75 kVA three-phase transformer is about 208.18 amps at 208 volts and 90.21 amps at 480 volts on the secondary.
ConversionsHow many amps is 45 kVA at 480V?
About 54.13 amps, three-phase (45,000 ÷ (√3 × 480)).
ConversionsWhat is the difference between kVA and kW?
kW is real power — the useful work — while kVA is apparent power, the total the conductors carry. They are linked by power factor: kW = kVA × power factor.
ConversionsHow do I convert kVA to amps for three-phase?
Divide by √3 times the line-to-line voltage: amps = kVA × 1000 ÷ (1.732 × volts). For example, 112.5 kVA at 480 volts is about 135.32 amps.
ConversionsHow many amps is 10 kVA?
About 41.67 amps at 240 volts single-phase, or 27.76 amps at 208 volts and 12.03 amps at 480 volts on three-phase.
Dr. Artie Vance
Dr. Artie Vance
Technical reviewer · Ph.D. in Physics, MIT · 14 years' experience · Formulas verified against IEEE / NEC conventions

This calculator gives estimates from the standard apparent-power formula. Transformer overcurrent protection and feeder sizing follow NEC 450.3 and your local authority having jurisdiction (AHJ) — always confirm against the code, and for larger installations, use a licensed electrician or engineer.