Note: this chart covers NEC building wire — the wire behind your walls and panel — not car audio, marine, or speaker wire gauge, which use different ampacity assumptions.
Most homes use copper wire. Use the 75°C column unless you know your breaker and outlets are rated higher — that's the standard rating for most modern panels and receptacles. If you're bundling several wires together or running through a hot attic, keep reading past the chart, because that 75°C number can still drop.
| AWG | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C |
|---|---|---|---|---|---|---|
| 14 | 15A | 20A | 25A | — | — | — |
| 12 | 20A | 25A | 30A | 15A | 20A | 25A |
| 10 | 30A | 35A | 40A | 25A | 30A | 35A |
| 8 | 40A | 50A | 55A | 35A | 40A | 45A |
| 6 | 55A | 65A | 75A | 40A | 50A | 55A |
| 4 | 70A | 85A | 95A | 55A | 65A | 75A |
| 3 | 85A | 100A | 115A | 65A | 75A | 85A |
| 2 | 95A | 115A | 130A | 75A | 90A | 100A |
| 1 | 110A | 130A | 145A | 85A | 100A | 115A |
| 1/0 | 125A | 150A | 170A | 100A | 120A | 135A |
| 2/0 | 145A | 175A | 195A | 115A | 135A | 150A |
| 3/0 | 165A | 200A | 225A | 130A | 155A | 175A |
| 4/0 | 195A | 230A | 260A | 150A | 180A | 205A |
Values assume not more than three current-carrying conductors, 30°C (86°F) ambient — NEC Table 310.16. Highlighted rows (14/12/10 AWG) get a separate overcurrent cap below.
Why 14, 12 and 10 AWG don't get their full table rating
NEC 240.4(D) caps small copper conductors regardless of insulation type: 14 AWG at 15A, 12 AWG at 20A, 10 AWG at 30A. Aluminum and copper-clad aluminum sit one step lower: 12 AWG at 15A, 10 AWG at 25A.
Line up those capped numbers against the chart above and they match the 60°C column exactly. The rule locks small conductors to their 60°C rating no matter what insulation you use, because most breaker and lug terminals are only rated for 60°C or 75°C — the wire's higher-temperature rating doesn't help if the connection point can't take it.
Ambient temperature derating
Table 310.15(B)(1) requires a correction factor once ambient temperature climbs past the 30°C (86°F) baseline. A conductor with 90°C insulation running through 36-40°C (96-104°F) ambient — a hot attic in summer — gets multiplied by 0.91. Go up to 41-45°C and the factor drops to 0.87.
Bundling / conductor-count derating
Table 310.15(C)(1) kicks in once you bundle 4 or more current-carrying conductors in the same raceway or cable. Four to six conductors get an 80% (0.80) adjustment factor, seven to nine drop to 70%, and it keeps falling as the bundle grows.
Worked example: heat + bundling together
Neither derating factor is hard on its own — the mistake is applying only one and stopping. Here's both, chained, for the scenario in the widget above.
- Read the 90°C base ampacity off the chart: 10 AWG copper = 40A.
- Apply the ambient correction for 36-40°C: 40A × 0.91 = 36.4A.
- Apply the bundling adjustment for 4-6 conductors: 36.4A × 0.80 = 29.12A.
- Check against the 240.4(D) cap for 10 AWG (30A) — 29.12A is already lower, so the derated number governs.
- Round down to the nearest standard breaker size (NEC 240.6(A)): 25A.
That same 10 AWG wire in a cool basement with only two conductors keeps its full 30A-capped rating. The heat and the bundling cost 5 amps here, not the gauge.
Copper vs. aluminum at the same gauge
Aluminum runs roughly one full gauge size behind copper for the same ampacity — a 2 AWG aluminum conductor carries less current than a 2 AWG copper conductor at every temperature rating in the chart. That's a real conductivity difference, which is why aluminum feeders are typically sized up rather than swapped in gauge-for-gauge.
This chart's values are NEC 2026 numbers. NEC 2026 is published, but state-by-state adoption is still in progress and moves at different speeds in different jurisdictions — check your local adopted edition rather than assuming one nationwide date. Section numbers can shift slightly between editions; the ampacity values themselves have stayed consistent. Confirm the current section numbers with your inspector before citing them on a permit.
Common ampacity mistakes
The most common one is sizing a breaker off the 90°C column directly, ignoring that most terminals are only rated for 60°C or 75°C. Close behind is skipping derating entirely on a bundled or attic run — a wire that's fine in a cool basement can be overloaded in a hot attic even with an identical breaker. Using aluminum ampacity numbers on a copper wire (or the reverse) is a smaller but real one too.
Frequently asked questions
Wire & CircuitIs a wire gauge amp chart the same for house wiring and car audio?
⚡ Wire Size calculator →
Code & SafetyCan I use the 90°C ampacity of a THHN wire to size my breaker?
Wire & CircuitWhy is 12 AWG copper wire rated for 20A instead of 25A or 30A?
⚡ Breaker Size calculator →
Code & SafetyDo I need to derate wire in a hot attic?
Wire & CircuitHow many wires can I bundle before I have to derate for conductor count?
Code & SafetyWhich NEC edition's numbers does this chart use?
This guide is for general information based on the National Electrical Code. Local codes and your authority having jurisdiction (AHJ) may differ. Electrical work can be dangerous, so when in doubt, hire a licensed electrician.