Open calculator
Wire Size · NEC 310.16 / 334.80

What Size Wire for a 60 Amp Breaker? 6 AWG vs 4 AWG, Conduit vs Romex

A 60 amp breaker needs 6 AWG copper in conduit — but 4 AWG copper in Romex. That's not a contradiction: 6 gauge only carries 60 amps as conduit wire, and the NM-B "Romex" on the shelf is rated lower. This is the one breaker size where the wire type changes the answer, so it's also the one that fails the most inspections. Here's how to get it right.

Dr. Artie Vance Written and reviewed by Dr. Artie Vance, Ph.D. Physics, MIT · 14 years' experience · Updated August 20, 2026
60A Wire Checker NEC 310.16
Will your wire pass at 60 amps?
Pick your wiring method and copper gauge — see if it clears a 60 amp breaker.
Method
Gauge
PASS ✓
65 A
clears the 60 A breaker
6 AWG copper as THHN in conduit is rated 65 A (75°C) — above 60 A ✓
Aluminum, length or another breaker size? Open the calculator →
A quick teaching check for 60 A copper. For aluminum, exact run length, or other breaker sizes, use the full calculator.

The quick answer

For a 60 amp circuit, use 6 AWG copper if you're running conduit (THHN/THWN), or 4 AWG copper if you're running NM-B "Romex". In aluminum, use 4 AWG. The equipment ground is 10 AWG copper either way.

If you just want one number

Not sure of your wire type, or want one size that's always right? Run 4 AWG copper. It carries 60 amps in conduit and in Romex, so you can't get it wrong — which is exactly why a lot of electricians default to it at 60 amps.

Why 60 amps is the tricky one: 6 AWG is at its limit

Most breaker sizes have one obvious wire. 60 amps doesn't, because it lands right on the edge of what 6 AWG copper can do — and where it lands depends on the wire's temperature rating.

  • 6 AWG copper as THHN/THWN in conduit (the 75°C column) = 65 amps → fine for a 60 amp breaker.
  • 6 AWG copper as NM-B "Romex" (limited to the 60°C column, NEC 334.80) = only 55 ampsunder 60, so it's not allowed.
⚠ 6 AWG Romex fails at 60 amps

This is the mistake that fails inspections. The 6-gauge Romex on the shelf is a 55-amp conductor — you cannot put it on a 60 amp breaker. Either pull 6 AWG THHN in conduit, or step the cable up to 4 AWG, which is 70 amps even at the 60°C Romex rating.

That's why "4 AWG copper" is the safe, universal answer: it clears 60 amps in every wiring method, so you never have to think about which column applies.

60 amp wire size chart

Every conductor in a 60 amp circuit, with the wire-type split made explicit:

ConductorCopperAluminum
Circuit wire — THHN in conduit (75°C)6 AWG4 AWG
Circuit wire — NM-B / Romex (60°C)4 AWG4 AWG *
Safe all-round choice4 AWG4 AWG
Equipment ground (NEC 250.122)10 AWG8 AWG

* Aluminum works differently from copper here. There's no 60°C aluminum "Romex" for feeders — aluminum comes as SER or USE cable rated 75°C, where 4 AWG aluminum carries 65 amps. So aluminum doesn't have copper's Romex trap; 4 AWG is the aluminum answer either way. The equipment ground stays 10 AWG copper for a 60 amp circuit — the same ground size the code uses all the way from 30 up to 60 amps, and in cable it's already included.

What a 60 amp circuit usually powers

Sixty amps is a common "medium feeder" size. By far the most frequent use is a subpanel — feeding a detached garage, a shop, or a finished basement. After that come hot tubs and spas, EV chargers (a 48-amp charger runs on a 60 amp circuit), welders, smaller electric ranges, and some AC or electric-heat equipment. If yours is a subpanel, there's an extra wiring rule worth getting right — it's the next section.

⚠ Hot tubs need GFCI

If your 60 amp circuit feeds a hot tub or spa, NEC Article 680 requires GFCI protection — usually a 60 amp GFCI breaker — plus a disconnect within sight of the tub. It doesn't change the wire size, but budget for the GFCI breaker and confirm the disconnect with your inspector.

Wiring a 60 amp subpanel: the 4-wire feeder

A subpanel is not wired like a simple 240-volt appliance. It needs a 4-wire feeder: two hots, a neutral, and a separate equipment ground. So the cable is 6/3 or 4/3 with ground — never 6/2.

⚠ Keep neutral and ground separate at the subpanel

At a subpanel, the neutral bar must be isolated from the ground bar and the enclosure — they're only bonded together back at the main panel. Removing the bonding screw and adding a separate ground bar is required (NEC 250.32 / 408.40). Tying neutral and ground together at a subpanel is the single most common — and most dangerous — subpanel mistake.

Is a 60 amp subpanel enough?

For most detached garages and shops, yes. A 60 amp subpanel comfortably runs lighting, general outlets, and one big load — a welder, an air compressor, or an EV charger — with room to spare. Where 60 amps gets tight is when you want to run several big loads at once, or add electric heat: a 50-amp welder plus a 48-amp EV charger plus a space heater will out-pull a 60 amp feeder.

The honest way to decide is a quick load calculation rather than a guess. If you're adding electric heat, a second big machine, or planning ahead for an EV, stepping up to a 100 amp subpanel is often the smarter long-term call — the wire costs a little more now and saves a re-pull later. Run your actual loads through the calculator before you commit.

Copper vs aluminum for 60 amps

Aluminum is the budget option on 60 amp feeders — 4 AWG aluminum (65 amps at 75°C) in conduit, or a step larger in 60°C cable. Copper is 6 AWG in conduit or 4 AWG in Romex. Aluminum SER is common on garage-subpanel runs where the cost savings add up over distance.

If you go aluminum, treat the terminations properly: aluminum-rated lugs and breakers, antioxidant compound, and torque to spec. For an indoor subpanel run you'll often see aluminum sold as SER cable (for example a 4-4-4-6 aluminum SER for a 60 amp feeder — two hots, a neutral, and a ground), while an outdoor or buried run uses direct-burial USE conductors or THWN in conduit. For the full ampacity behind these numbers, see the AWG ampacity chart.

One more subpanel detail: the panel itself can be a main-lug type (no main breaker, protected by the 60 amp breaker back at the source) or a main-breaker type. Either works for a 60 amp feeder; a main-breaker subpanel just adds a convenient local shutoff, which many people like in a detached shop.

Long runs and voltage drop

Because 60 amp circuits so often feed a detached building, voltage drop matters. Keeping the drop under 3% (an Informational Note under 210.19(A) — advisory, not a hard limit) is the goal on a long run.

Distance before 3% drop (full 60A, 240V)

6 AWG copper → about 122 ft.
4 AWG copper → about 194 ft. On a long garage or shop feeder past these, step up a size — another reason 4 AWG is a popular default at 60 amps.

The Voltage Drop Calculator runs your exact length, load, and material in one step.

How 40, 50 and 60 amp wire compare

If you're deciding between breaker sizes, here's how the three common mid-range circuits line up. Notice the pattern: the jump from 50 to 60 amps is where copper crosses the line that forces the conduit-vs-Romex choice.

BreakerCopperAluminum
40 amp8 AWG6 AWG
50 amp6 AWG4 AWG
60 amp6 AWG (conduit) / 4 AWG (Romex)4 AWG

A 50 amp circuit is comfortable on 6 AWG copper in either Romex or conduit; at 60 amps that same 6 AWG only clears in conduit. If you're on the fence between 50 and 60, that wire-type wrinkle is worth factoring in.

Common 60 amp wiring mistakes

The signature one is putting 6 AWG Romex on a 60 amp breaker — it's a 55-amp conductor, so it's undersized and a real fire risk. Close behind is reading the 90°C column (75 amps) to justify going smaller; your terminals are 60 or 75°C, so that column doesn't apply. Then the subpanel errors: bonding neutral and ground together at the subpanel, or running 6/2 where a subpanel needs the neutral in 6/3. And on the long feeders 60 amps so often involves, forgetting voltage drop. As always, this is usually permit-and-inspection work, so confirm with your AHJ.

Frequently asked questions

Wire & CircuitWhat size wire do I need for a 60 amp breaker?
6 AWG copper if you run THHN in conduit, or 4 AWG copper if you run NM-B Romex, because 6 AWG Romex is only rated 55 amps. In aluminum, use 4 AWG. The ground is 10 AWG copper.
⚡ Wire Size calculator →
Wire & CircuitIs 6 gauge wire good for 60 amps?
Only as THHN/THWN in conduit, where 6 AWG copper is rated 65 amps. As NM-B Romex it's only 55 amps, which is under a 60 amp breaker, so Romex needs 4 AWG.
Code & SafetyCan I use 6 AWG Romex for a 60 amp circuit?
No. NM-B Romex is limited to the 60°C column, where 6 AWG carries only 55 amps — under a 60 amp breaker. Use 4 AWG copper in Romex, or 6 AWG THHN in conduit.
Wire & CircuitWhat size wire for a 60 amp subpanel?
The same conductors — 6 AWG copper in conduit or 4 AWG in Romex — but run as a 4-wire feeder (6/3 or 4/3 with ground), with the neutral and ground kept separate at the subpanel.
Wire & CircuitWhat size aluminum wire for 60 amps?
4 AWG aluminum, which is rated 65 amps at 75°C. Aluminum feeder cable (SER or USE) is 75°C-rated, so unlike copper Romex it doesn't drop below 60 amps — 4 AWG is the standard answer, and it's common on longer subpanel feeders to save cost.
Code & SafetyWhat size ground wire for a 60 amp circuit?
10 AWG copper (or 8 AWG aluminum) per NEC Table 250.122 — the same equipment ground used from 30 up to 60 amps. In cable it's already included.
Wire & CircuitWhat gauge wire for a 60 amp 240V circuit?
The same as any 60 amp circuit — 6 AWG copper in conduit or 4 AWG in Romex. The 240 volts doesn't change the gauge, only the number of conductors you run.
Wire & CircuitHow far can I run 6 AWG wire on a 60 amp circuit?
At a full 60 amp load on 240V, roughly 122 ft before exceeding a 3% voltage drop; 4 AWG copper reaches about 194 ft. Longer feeders should step up a size.
⚡ Voltage Drop calculator →
Dr. Artie Vance
Dr. Artie Vance
Technical reviewer · Ph.D. in Physics, MIT · 14 years' experience · Cross-checked against NEC 2026 & 2026

This guide is for general information based on the National Electrical Code. Local codes and your authority having jurisdiction (AHJ) may differ, and subpanel and feeder work is usually permit-and-inspection territory. Electrical work can be dangerous, so when in doubt, hire a licensed electrician.