What Size Wire for a 200 Amp Service? Copper, Aluminum & the 310.12 Dwelling Rule

For a normal house, a 200 amp service uses 2/0 AWG copper or 4/0 AWG aluminum — not the 3/0 copper you'll see quoted all over the internet. The reason is one NEC rule most guides skip: the dwelling 83% rule (310.12). Here's why 2/0 is legal, when you actually need 3/0, what size ground wire to run, and how far you can go before upsizing.

Dr. Artie Vance Written and reviewed by Dr. Artie Vance, Ph.D. Physics, MIT · 14 years' experience · Updated August 20, 2026
Wire Size Calculator · Sample NEC 310.12 / 250.66
200A service · single-family dwelling · copper
2/0 AWG copper
+ 4 AWG copper grounding electrode conductor
310.12 → 200 A × 83% = 166 A required → 2/0 Cu = 175 A (75°C) ✓ → GEC #4 Cu (250.66)
Check your service size, material & run →
Aluminum, a non-dwelling service, or a long feeder to a detached building? This is one fixed example — the calculator runs the NEC math for your exact setup.

The quick answer

For a standard 200 amp residential service, run 2/0 AWG copper or 4/0 AWG aluminum. Most homes actually use aluminum, so the cable you'll usually buy is 4/0-4/0-2/0 aluminum SER (two 4/0 hots and a 2/0 neutral).

If you just want one number

House with a 200 amp panel? 2/0 copper or 4/0 aluminum for the two hot conductors. If a source tells you 3/0 copper, it's quoting the commercial number — legal, but a size bigger and more expensive than your house needs. The next section explains exactly why.

Why it's 2/0 copper, not 3/0 (the 310.12 dwelling rule)

This is the part almost every other guide gets wrong. There's a special NEC rule for homes: 310.12, often called the 83% rule. It lets the main service conductors (and the main feeder) that carry a dwelling's entire load use wire rated for just 83% of the service rating, because a house never actually pulls its full rated amperage continuously.

Run the math for a 200 amp service:

  1. 200 A × 83% = 166 A — that's the ampacity your wire actually has to have.
  2. Look up 166 A in the 75°C column: 2/0 copper carries 175 A and 4/0 aluminum carries 180 A — both clear 166 A.
  3. So a 200 amp home service is legal on 2/0 copper / 4/0 aluminum, one size smaller than a commercial feeder.

That single rule is why the wire behind almost every 200 amp residential meter in the country is 2/0 copper or 4/0 aluminum — and why paying for 3/0 copper on a normal house is usually money spent on a size you don't need.

When you actually use 3/0 copper (the standard value)

The 83% rule only applies to dwellings, on the conductors carrying the whole load. Step outside that and you're back to the full ampacity table, NEC 310.16, where 200 amps needs 3/0 copper (200 A) or 250 kcmil aluminum (205 A) at 75°C.

SituationCopperAluminum
Home service / main feeder (310.12, 83%)2/0 AWG4/0 AWG
Commercial or non-dwelling (Table 310.16)3/0 AWG250 kcmil

You'd use the 3/0 column for a commercial 200 amp service, a sub-feed that doesn't carry the full dwelling load, or any time your local inspector (AHJ) specifically asks for full-table sizing. When in doubt, ask the AHJ before you buy — it's a one-question phone call that can save a size either way.

200 amp service wire chart

Every conductor in a typical 200 amp residential service, in one place:

ConductorCopperAluminum
Hot conductors (dwelling, 310.12)2/0 AWG4/0 AWG
Neutral (sized to load, 220.61)often 1 size downe.g. 2/0 on 4/0 SER
Grounding electrode conductor (250.66)4 AWG2 AWG
GEC to ground rods only (250.66(A))6 AWG4 AWG

The neutral (grounded conductor) doesn't have to match the hots — it's sized to the unbalanced 120-volt load under 220.61, which is why standard SER cable comes as 4/0-4/0-2/0: full-size hots, a smaller neutral.

100, 200 and 400 amp service wire (quick reference)

The same 310.12 dwelling rule sizes every residential service, so if you're comparing panels — or upgrading — here are the three common ratings side by side. Each is the 83% dwelling value, the size a normal house actually uses.

ServiceCopper (dwelling)Aluminum (dwelling)
100 amp4 AWG2 AWG
200 amp2/0 AWG4/0 AWG
400 amp400 kcmil600 kcmil

These are the conductors that carry the whole service. Whether they run as SER cable through the wall or as individual THWN/XHHW conductors in conduit doesn't change the size — it only changes the cable type. A 200 amp upgrade from an older 100 amp panel, for example, steps the hots from 4 AWG copper all the way up to 2/0.

What size ground wire for a 200 amp service?

This is the second-most-asked question about 200 amp services, and it's confusing because "ground wire" can mean two different things. Let's separate them.

The grounding electrode conductor (GEC) — the wire from your panel to the ground rods, water pipe, or Ufer — is sized by NEC Table 250.66. For a 200 amp service with 2/0 copper conductors, that's 4 AWG copper.

The ground-rod shortcut

There's a common allowance in 250.66(A): where the GEC connects only to a ground rod (or rods), it never has to be larger than 6 AWG copper, no matter the service size. So the wire to your ground rods can be #6, while the main GEC to a concrete-encased electrode (Ufer) is #4. Both are correct — they serve different electrodes.

Don't confuse the GEC with the neutral in the service cable — that's the third conductor sized under 220.61, not a "ground." Mixing them up is the single most common error in the ground-wire questions.

Copper vs aluminum for a 200 amp service

At service-entrance sizes, the cost gap between copper and aluminum is large, which is why 4/0 aluminum SER is what most homes are wired with. Copper (2/0) shows up where an installer prefers it, where terminations demand it, or on shorter runs where the price difference is small. Neither is "better" — both are code-compliant at the sizes above.

If you go aluminum, treat the connections properly: aluminum-rated lugs and breakers, an antioxidant compound on the terminations, and torque to the manufacturer's spec. Done right, aluminum service conductors have a long, reliable track record; done carelessly, loose aluminum terminations are a real hazard. For the underlying ampacity behind all of these numbers, see the full AWG ampacity chart.

Service entrance cable: SER, SEU, or conduit?

The 2/0 copper or 4/0 aluminum conductors reach your panel one of three common ways, and the wire size is the same in all of them — only the cable type changes with the path:

  • SER (Service Entrance, Round) — a four-conductor cable with two hots, a neutral, and a bundled ground. Used for the main feeder from the disconnect to the panel, and for subpanels. This is the classic 4/0-4/0-2/0 aluminum SER.
  • SEU (Service Entrance, U-shaped) — three conductors, no separate ground. Used from the meter to the main service disconnect, where the neutral is still bonded to ground.
  • THWN / XHHW in conduit — individual conductors pulled through pipe for exposed, outdoor, or underground runs (underground typically uses USE/RHW-rated wire).

If you're going underground from a pad-mount transformer or a detached meter, the run is almost always individual conductors in conduit rather than cable. Your utility and local AHJ set the exact rules at the service point, so confirm the required type before you buy.

Meter to panel, and long runs (voltage drop)

The service-entrance run — meter base to main panel — is usually short, so the dwelling sizes above are all you need. Voltage drop only becomes a factor on a long feeder, like a 200 amp subpanel in a detached garage or shop far from the house.

Distance before voltage drop bites (full 200A, 240V, 3%)

2/0 copper → good to about 186 ft.
4/0 aluminum → good to about 180 ft. Past that on a long feeder, step the conductors up a size.

One thing to keep straight: the NEC sets no hard voltage-drop limit on a service or feeder — the 3% figure is a recommendation (an Informational Note), not a rule you can fail inspection on. It's still worth following on long runs so lights don't dim when the AC kicks on. The Voltage Drop Calculator checks your exact distance and load.

Common 200 amp service mistakes

The most expensive one is buying 3/0 copper when 2/0 is legal for a house — a full wire size of copper you didn't need. The opposite error is applying the 83% rule where it doesn't belong, like a non-dwelling service. After that it's grounding: undersizing the GEC, or confusing the grounding electrode conductor with the neutral. Aluminum installs fail when terminations aren't torqued or anti-oxidant is skipped. And the quiet one — assuming a national answer when your local AHJ has amended the code; always confirm locally before a service job.

Frequently asked questions

Service & CodeWhat size wire do I need for a 200 amp service?
For a standard home, 2/0 AWG copper or 4/0 AWG aluminum, under the NEC 310.12 dwelling rule. Non-dwelling services use the larger 3/0 copper or 250 kcmil aluminum.
⚡ Wire Size calculator →
Service & CodeIs 2/0 or 3/0 copper right for a 200 amp service?
2/0 copper for a house. NEC 310.12 lets a dwelling's service conductors carry the load at 83% of the rating, so 200 amps only needs wire rated for 166 amps, which is 2/0 copper. 3/0 copper is the full-table value for non-dwelling services.
Wire & CircuitWhat size aluminum wire for a 200 amp service?
4/0 AWG aluminum for a residential service under the 310.12 dwelling rule. A non-dwelling 200 amp service uses 250 kcmil aluminum. Aluminum SER is the most common 200 amp service cable in homes.
Service & CodeWhat size ground wire for a 200 amp service?
The grounding electrode conductor is 4 AWG copper per NEC Table 250.66. Where it connects only to ground rods, 250.66(A) allows it to be as small as 6 AWG copper.
Wire & CircuitCan I use 4/0 aluminum for a 200 amp service?
Yes. 4/0 aluminum is the standard, code-compliant choice for a 200 amp residential service and is used more often than copper because it costs far less at this size.
Service & CodeWhat is the 83% rule for service conductors?
NEC 310.12 lets the main service or feeder conductors of a dwelling be sized at 83% of the service rating, because a home never draws its full rating continuously. It's why a 200 amp house service needs only 166 amps of ampacity (2/0 copper).
Wire & CircuitHow far can I run 2/0 copper on a 200 amp service?
At a full 200 amp load on 240V, roughly 186 ft before exceeding a 3% voltage drop; 4/0 aluminum reaches about 180 ft. Long feeders to detached buildings past that should step up a size.
⚡ Voltage Drop calculator →
Service & CodeWhat size wire runs from the meter to the panel for a 200 amp service?
The same dwelling sizes: 2/0 copper or 4/0 aluminum. The meter-to-panel run is the main service conductor, so the 310.12 dwelling rule applies, and because the run is usually short, voltage drop isn't a factor.
Dr. Artie Vance
Dr. Artie Vance
Technical reviewer · Ph.D. in Physics, MIT · 14 years' experience · Cross-checked against NEC 2026 & 2026

This guide is for general information based on the National Electrical Code. Local codes and your authority having jurisdiction (AHJ) may differ, and service work is often permit-and-inspection territory. Electrical work can be dangerous, so when in doubt, hire a licensed electrician.